Brick-S.S. Fire Rating
folderbar.jpg

[HOME] [TECH LIBRARY] [FIRE SAFETY] [Masonry UL Ratings] [Brick Fire Ratings]

Related External Links

BIA Tech Note 16

NCMA Techical Notes

BIA Tech Note 16b

UL Web Site

 

Brick & Steel Stud

UL Fire Ratings

Search for Masonry Articles

 

 

 

UL Number

Fire Rating

Description of Assembly

U418

45 min

to

2 hrs

Brick Veneer / Steel Stud, Loadbearing

  • (45 min): (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • (1 hr): (2) layers in. (12.7 mm) thick gypsum wallboard
  • (2 hr): (3) layers in. (12.7 mm) thick gypsum wallboard
  • 3 or 5 in., (89 or 140 mm) 18 gage, steel studs, spaced at 24 in. (610 mm) o.c., with 3 in.(89 mm) thick glass fiber batt insulation
  • (1) layer in. (12.7 mm) thick exterior gypsum sheathing
  • 1 in. (25.4 mm) air space
  • 4 in. (102 mm) nominal clay facing brick laid in mortar with metal ties at 24 in. (610 mm) o.c. horizontally and 16 in. (406 mm) o.c. vertically

U424

45 min.

to

2 hrs

Brick Veneer / Steel Stud, Loadbearing

  • (45 min): (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • (1 hr): (2) layers in. (12.7 mm) thick gypsum wallboard
  • (1 1/2 hr): (2) layers ⅝ in. (15.9 mm) thick gypsum wallboard
  • (2 hr): (3) layers in. (12.7 mm) or (2) layers in. (19.1 mm) thick gypsum wallboard
  • 3 in. (89 mm), 20 gage steel studs, spaced up to 24 in. (610 mm) o.c., with 3 in. (89 mm) thick glass fiber or mineral wool batt or blanket insulation
  • (1) layer or ⅝ in. (12.7 or 15.9 mm) thick exterior gypsum sheathing
  • Air space thickness not specified
  • 3 in. (95 mm) min. brick veneer with corrugated metal wall ties attached to each stud with steel screws, not more than each sixth course of brick

U425

45 min.

to

2 hrs

Brick Veneer / Steel Stud, Loadbearing

  • (45 min): (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • (1 hr): (2) layers in. (12.7 mm) thick gypsum wallboard
  • (1 1/2 hr): (2) layers ⅝ in. (15.9 mm) thick gypsum wallboard
  • (2 hr): (3) layers in. (12.7 mm) or (2) layers in. (19.1 mm) thick gypsum wallboard
  • 3 in. (89 mm), 20 gage steel studs, spaced up to 24 in. (610 mm) o.c., with 3 in. (89 mm) thick glass fiber or mineral wool batt or blanket insulation
  • (1) layer or ⅝ in. (12.7 or 15.9 mm) thick exterior gypsum sheathing
  • Air space thickness not specified
  • 3 in. (95 mm) brick veneer with corrugated metal wall ties attached to each stud with steel screws, not more than each sixth course of brick

V434

1 hr

Brick Veneer / Steel Stud, Loadbearing

  • (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • 3 in. (89 mm), 20 gage, steel studs with max. spacing at 24 in. (610 mm) o.c., with 3 in.(89 mm) thick glass fiber batt insulation
  • 2 in. (51 mm) max. thick foamed plastic
  • 1 in. (25.4 mm) min. air space
  • 4 in. (102 mm) nominal brick veneer with wall anchor ties attached to studs at max. 24 in.(610 mm) o.c.

V454

1 hr

Brick Veneer / Steel Stud, Loadbearing

  • (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • 3 in. (89 mm), 20 gage, steel studs at max. spacing of 24 in. (610 mm) o.c.
  • (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • 4 in. (102 mm) max. thick rigid polystyrene insulation
  • 1 in. (25.4 mm) min. air space
  • 4 in. (102 mm) nominal brick veneer with wall anchor ties attached to studs at max. 24 in.(610 mm) o.c.

V458

45 min

Brick Veneer / Steel Stud, Loadbearing

  • (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard bearing UL Classification Mark
  • 3⅝ in. (92 mm) 18 gage steel studs at max. spacing of 24 in. (610 mm) o.c. with nominal 3.5 pcf mineral wool batt
  • (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • 1 in. (25.4 mm) min. air space
  • 3 in. (95 mm) min. thick brick veneer with corrugated metal wall ties attached to each stud with steel screws, not more than each sixth course of brick

V414

3hr interior

1hr exterior

Brick Veneer / Steel Stud,

NON-Loadbearing

  • (1) layer ⅝ in. (15.9 mm) thick gypsum wallboard
  • 3⅝ in. (92 mm) wide, 1⅝ in. (41 mm) legs, 20 gage steel studs, spaced 16 in. (406 mm) o.c., studs cut in. (19.1 mm) less than assembly height
  • 2 in. (51 mm) thick foamed plastic (rigid insulation)
  • 2 in. (51 mm) air space
  • 4 in. (102 mm) nominal clay facing brick laid in mortar with metal ties at 16 in. (406 mm) o.c. max. each way