CORRUGATED TIES NOT PERMITTED IN COMMERCIAL CONSTRUCTION

Item I:

1. Corrugated wall ties are only allowed, by code, to be used in veneer work on wooden studs.

2. If brick is veneered over concrete block, or concrete backing- only wire anchors, adjustable anchors or joint reinforcement is allowed by code. That is the LAW! Copy enclosed. [85 to 90% of corrugated ties used in the Chicagoland area, with block backup, is by non union, or very uneducated bricklayers. 10 to 15% is by local residential bricklayers, who are moving up from residential wooden framed veneer, to brick with block backup for small commercial construction. By the way, where is the architect on this job? What is called for on the drawings?

On the drawings (under Mandatory Specifications Checklist in the ACI 530 Code, Notes to Architect / Engineer), specify the location, spacing and type of accessories not indicated on the project drawings.

Item II:

If the brick & block wall has already been laid up with corrugated ties, then a retro tie will have to be installed, by drilling and installing such anchor. (Copy enclosed.)  If the block has been laid up with corrugated ties and the brick veneer has not been laid up yet, another option is to install D/A 5213 anchors onto the CMU backup and a wire pintle should be installed to tie the brick veneer to the backup.

Item III:

On all exterior walls- all joint reinforcement, wire ties, or wire anchors, minimally must be hot dipped galvanized- to ASTM A153 (1.5 oz/ft2) (That is the law!)

How can you tell it is hot dipped compared to just mil galvanized? (They both look silver!) For wire reinforcing, it comes banded together and is labeled, HD, on the end of each bundle. Individual hot dipped pieces look like they were dipped in a trough of silver paint and the metal is encapsulated.          
 

corrugated.JPG

This project addition in the western suburbs used corrugated ties and had other major masonry problems. It has since been torn down and will be rebuilt in the spring.

cavitycorrugated copy.jpg

In this example, the use of corrugated ties in a brick / block cavity wall is illegal and not built to code!

From Building Code Requirements for Masonry Structures (ACI 530-99/ASCE 5-99/TMS 402-99)

6.2.2.8 Masonry Veneer anchored to masonry or concrete backing

    6.2.2.8.1 Attach veneer to masonry backing with wire anchors, adjustable anchors or joint reinforcement.

2.4 F Coatings for corrosion protection

    b. Joint reinforcement, wire ties, or wire anchors in exterior walls exposed to a mean relative humidity exceeding  75 percent (for example, natatoria and food processing)  ASTM A153 (1.50 oz/ft2)

EXAMPLES OF SUGGESTED ANCHORS TO USE IF A BRICK VENEER WAS INCORRECTLY LAID UP USING CORRUGATED TIES

helifix logo31_Copy51

hb.gif

duroflex.tif

WWW.HELIFIX.COM

WWW.H-B.COM

WWW.DUR-O-WAL.COM

helifix.tif
spiro40_Copy47
duroflex.tif
FROM : RESTORATION SUPPLY INC.  773-472-3575
FROM : BRACING SYSTEMS 630-665-2732
FROM : BRACING SYSTEMS 630-665-2732

EXAMPLES OF SUGGESTED ANCHORS TO USE IF BLOCK WAS LAID UP WITH CORRUGATED TIES AND BRICK NOT YET LAID (LEAVE CORRUGATED TIES IN PLACE - BENT UP OR DOWN)

Hlogo155_Copy31HECKMANN BUILDING PRODUCTS

hb.gif

duroflex.tif

WWW.HECKMANNBUILDINGPRODS.COM

WWW.H-B.COM

WWW.DUR-O-WAL.COM

75tcpx48_Copy42
75tapcon50_Copy41
TAPCON SCREW FOR BRICK VENEER TO CONCRETE BLOCK

hb20046_Copy43
HB-2OO

521344_Copy44
FROM : LANCE CONSTRUCTION  SUPPLY  773-522-1900
FROM : BRACING SYSTEMS 630-665-2732
FROM : LANCE CONSTRUCTION  SUPPLY  773-522-1900
HD165_Copy16

THIS IS AN EXAMPLE OF HOW JOINT REINFORCEMENT IS LABELED. THIS MAKES IT EASY TO DETERMINE THAT THE REINFORCEMENT USED IS INDEED HOT DIPPED

 

Picture

{HOME} {TECHNICAL LIBRARY} {INDUSTRY DIRECTORY}